Automation and Device Networking – M.A.P.P.
Wireless RF Modem Site Survey
Laptop Connection
- Connect the 9XTend RF modem to the laptop using a usb cable.
- Connect the 9Xtend power adapter.
- Install the latest X-CTU installer software: http://www.digi.com/support/productdetl.jsp?pid=3157&osvid=0&tp=5&tp2=0
Remote Site
-
The 9XTend RF modems have been tested up to 2 miles (3.21868 km) using the standard 2.1 dbi dipole antennas. The RF modems must have line of sight, with no obsticles blocking the path.
- The maximum legal antenna gain is + 6 dbi for a 1 watt transmitter @ 900 MHz. Combining a +8 dbi Yagi antenna with a 10 foot coaxial RF antenna (-2 dbi) will meet this requirement. The diagram below shows the components for the remote location. A good power invertor for the 9XTend will ensure a successful test.

X-CTU Software
- Select the PC Settings tab.
- Select the com port that is connected to the 9XTend.
- Select the Test/Query tab.
- A Com test/ Query Modem box will appear to confirm communication with the 9XTend modem, that is connected to the laptop.
- Select the Range Test tab.
- Select Loop Back and the Transmit tab.
- Select the Start tab and the stats will appear.
- When satisfied with the results click the Stop tab.
Weblinks
- http://www.digi.com/pdf/ds_xtend.pdf (9XTend brochure)
- http://www.fcc.gov/ (FCC - Federal Communications Commission)
- http://www.fcc.gov/oet/ea/presentations/files/oct05/Unlicensed_Devices_JD.pdf (Unlicensed Devices General Technical Requirements – see page 94)
-
http://www.ic.gc.ca/eic/site/ic1.nsf/eng/h_00000.html?OpenDocument (Industry Canada)
At Manufacturers Automation Inc., we are dedicated to customer service and want to make your experience with Adaptive a pleasant one.
© Copyright 2010, Manufacturers Automation Inc., www.manuauto.com
Manufacturers Automation Inc. 1600 King Street North P.O. Box 602 St. Jacobs, ON N0B 2NO 800-387-6268 Tel. 519-664-3300 Tel. 519-664-1600 Fax.
Moxa NPort 5150 Bench Test
by Brent Raynor www.manuauto.com
RS-232 and RS-485 Port Test
Windows XP Setup
- Change the properties of the Local Area Connection.
- Go to Start,Settings, and then Network Connections.
- SelectLocal Area Connection andthenProperties.
- Scroll down the list and select Internet Protocol (TCP/IP).IfIP information is shownunderUse the following IP address, make sure to write it down before proceeding.
- Select Use the following IP address and enter an IP addressthat issimilar totheNPort 5110, except for the last two digits.
Hardware Setup
- Connectanethernet cross-over cable from the computer to the NPort 5150.
Moxa NPort Management Suite
-
The first step is to configure the ethernet side of theNPort 5110.
-
Open theNPort Management Suiteand select Configuration.


-
Select the NPort (MAC Adress) andconfigure the settings.
-
SelectNetworkand modify the IP Address, NetMask, and Gateway.

-
SelectSerial, then select Modify, double clicktheinformation line and select theSettings.

-
Set the baud rate to 9600, 8,N,1, No flow Control, enable FIFO. The Interface tab is eitherset toRS-232 or RS-485, 4 wire, depending on what signalis being tested.

- SelectOperation Mode, then select the Modify tab, double clicktheinformation line and selectView Settings tab. Set it for Real Com Mode.
- SelectOK and the settings will be updatedin the NPort 5110.


-
The next step is to configurethe com port.
-
SelectCOM Mappingand double clicktheinformation line to change the serial settings. If there is no information is shown, select Add Target.

-
Select the NPort required and click OK.


-
SelectBasicSettings and choose a com port.

-
SelectSerial Parametersand set for 9600,8,N,1, no flow control.Click OK.

-
SelectExit.

Reboot the computer at this point, before doing the loopback test.
HyperTerminal Loopback Test
TesttheRS-232communication port
- Jumperpins 2 to3on theMoxa NPort DE-311 DB9 com port.
- Pin 2 -> TXD Pin 3 -> RXD
- InWindows XP,go to start, programs,accessories,communications, and select HyperTerminal.
- Type aname for this project.
-
Select the com port that was assigned inRealCOM Installer.

-
Com port settings are 9600, 8, N, 1, None. Click OK.

-
Type a message and it willappearon theHyperTerminalscreen. ThisconfirmstheRS-232 communication portworks accordingly. Test this procedure by removing the jumper. As you type, the characters will notappear on theHyperTerminalscreen.
TesttheRS-422/485communication port
- Jumperpins 2 to3 and1 to 4 on theMoxa NPort DE-311 DB9 com port usingtwopaperclips.
- Pin 2 -> RXD+(B) Pin 3 -> TXD+(B)
- Pin 1 -> RXD-(A) Pin4 -> TXD-(A)
- Repeatthe HyperTerminal Loopback Test.
At Manufacturers Automation Inc., we are dedicated to customer service and want to make your experience with Moxaa pleasant one.
© Copyright 2010, Manufacturers Automation Inc., www.manuauto.com
Manufacturers Automation Inc. 1600 King Street North P.O. Box 602 St. Jacobs, ON N0B 2NO 800-387-6268 Tel. 519-664-3300 Tel. 519-664-1600 Fax.
StreetSmart 17X Ethernet Port Configuration
by Brent Raynor www.manuauto.com
How to configure the StreetSmart ethernet port
-
Connect an RS232 cable to COM O of the Adaptive StreetSmart controller board

-
Open the Diagnostic program in the AlphaNet software
-
Configure the Serial Settings, 9600, 8, N, 1 and select OK

-
Select Set Custom Commands

- Select Command 3
- Select Open Ini File

- Input the IP address and Subnet Mask
- Type under Command 3 in capital letters
- _01Z00_02EUi010.001.001.060_04
- Type under Command 4 in capital letters
- _01Z00_02EUs255.255.255.000_04
- Save and close
When entering the IP address or subnet mask make sure to enter three numbers before each dot. ie. 010.011.011.254

- Select Command 3 and the button will turn on.
- Click on Refresh and the IP address will update.
- Select Send (takes 30 seconds to update the EPROM)

- Confirm the IP address in StreetSmart display by typing _01Z00_02FUi_04
- Select Enter Your Own Command Text
- and after 30 seconds the changes will appear in the Results box

- Recycle power on the StreetSmart led display and the new IP address will appear on the diagnostic startup of the display.
At Manufacturers Automation Inc., we are dedicated to customer service and want to make your experience with Adaptive a pleasant one.
© Copyright 2010, Manufacturers Automation Inc., www.manuauto.com
Manufacturers Automation Inc. 1600 King Street North P.O. Box 602 St. Jacobs, ON N0B 2NO 800-387-6268 Tel. 519-664-3300 Tel. 519-664-1600 Fax.
Wireless Site Survey – Model 1650 WiFi
by Brent Raynor www.manuauto.com
Recommended Procedure For A Sight Survey And Install
- Access point (receiver) 192.168.1.232
- Bridge (transmitter) 192.168.1.231
- Clear line of sight required, free of obstructions (ie. trees).
- Maximum distance between Acesss point and Bridge is 300 feet.

Changing your computer’s IP address to communicate with the Access point (sign side)
- Change the properties of the Local Area Connection.
- Go to Start, Settings, and then Network Connections.
- Select Local Area Connection and then Properties.
- Scroll down the list and select Internet Protocol (TCP/IP).
- Select Use the following IP address and enter an IP address that is similar to the Bridge, except for the last two digits.
- Connect an Ethernet crossover cable from the PC to the Bridge.

Site Survey using Windows Explorer
- Open Windows Explorer
- In the address bar type ftp://192.168.1.231 and click GO.

- At the login prompt, type admin for the Username and Password
- The EnGenius main screen will appear.
- Click on Wireless Network

- The Wireless Network screen will appear.
- Click the Site Survey button.

- The Site Survey sreen will appear.
- Look for the EnGenius radio. If not present, click the refresh button.
- If more than one EnGenius radio is present, refer to the MAC address of the radio required.
- The Signal column (dbm) in this window will show the signal strength.

Signal Strength Scale Guide
0 to -50 indicates Strong signal strength
-75 to -100 indicates Excellent signal strength
-51 to -75 indicates Good signal strength
At Manufacturers Automation Inc., we are dedicated to customer service and want to make your experience with Adaptive a pleasant one.
© Copyright 2010, Manufacturers Automation Inc., www.manuauto.com
Manufacturers Automation Inc. 1600 King Street North P.O. Box 602 St. Jacobs, ON N0B 2NO 800-387-6268 Tel. 519-664-3300 Tel. sales@manuauto.comDrive Traffic To Your Business
Adaptive is the leading supplier of led digital signage solutions. Introducing the Excite series, the next generation of full colour outdoor advertising solutions.
The Excite series has been designed to maximize return of advertising, while minimizing energy and maintenance costs. With bright displays and ultra wide viewing angles the Excite series is ideal for any on or off premise advertising application. With its light weight modular design, the Excite series provides edge to edge viewing without the wasted space seen on bulky framed in configurations and because it’s equipped with digital pure colour processing, the Excite series renders over 16 million vibrant colours that shine bright in all lighting conditions.
The Excite series is the first all digital led display to use an industry standard DVI architecture for maximise flexibility. This provides straight forward integration with in door signage networks for an enterprise solution and because every Excite ships with Ooh!Media, Adaptives’ powerful content, creation, and scheduling software. You will have the flexible to instantly deliver targeted exciting digital media that can be produced at a moments notice or scheduled months in advance.
With true Ethernet connectivity and embedded PC control, the Excite series delivers blazing fast file transfers and is capable of displaying real time video content, at up up to 60 frames per second.
Enclosed in Adaptives innovative protector case, environmental containments like dirt and salt spray are virtually eliminated from Excites internal compartments, minimizing maintenance costs and maximizing the life of your investment.
The Excite series is engineered and manufactured by Adaptive, a company with over 30 year of successfully delivering industry leading led display solutions and after sales support with a nation wide network of factory trained partners.
Courtesy of Adaptive
![]()
![]()
© Copyright 2010, Manufacturers Automation Inc., www.manuauto.com
Manufacturers Automation Inc. 1600 King Street North P.O. Box 602 St. Jacobs, ON N0B 2NO 800-387-6268 Tel. 519-664-3300 Tel. 519-664-1600 Fax.Panasonic Promotion for January 2010 – Fully Expandable PLC

During the Month of January 2010 only Panasonic Ideas for Life have a Fully Expandable PLC package for only $299.00 CAD. Touch Screen with pass through feature.
The package includes:
- 1 – PLC – AFPX-C14R
- 1 – 5ft Cable – AFC1500-US
- 1 – Touch Screen – AIGT0030B1
- 3 Year Warranty Included
- Plus PLC & HMI software package
- All for $299.00 (Regular value $407.00)
The regular price for this package is $407.00 but you can get the Fully Expandable PLC Package for $299.00 Canadian Dollars till the end of January.
Tamperproof XStream Wireless Modems
by Brent Raynor www.manuauto.com
Overview
MaxStream XStream wireless modems can now be security coded by applying a Vendor Identification (VID) number. This procedure will protect against unwanted intruders.
Procedure
- Connect the MaxStream XStream to the computer using a straight through serial cable.
- Only dip switch 1 is in the on position.
- Apply power to the XStream.
- Open the MaxStream X-CTU software. Should a Windows error box appear it means the XStream unit is not connected to the computer.
- Select the Modem Configuration tab and the Read tab to acquire the modem parameters. A Version box will appear. In order for this procedure to work change the version to 42B5 .

- Select the Write tab and at the bottom of the screen will appear Complete.

- Select the Terminal tab to enter AT commands.
- Holding down the the shift key and typing +++ simutaenously will acknowledge an OK. If necessary repeat this step until you see the OK.
- Continue the following steps in a timely manner or you will have to repeat the above step.

- Type atid and the VID code of the modem will appear in red.

- Type atid 4444 as the new number and press the Enter Key. The Ok will appear.

- This new number must be saved to non-volatile memory using a Write Command (ATWR) . Otherwise, the VID code revert to the original number when the modem is powered off and then on again.
- Type atwr and press the Enter Key. OK will appear.

- Type atcn to exit the command mode.
- Repeat this step for the corresponding XStream wireless modem.

http://ftp1.digi.com/support/documentation/productmanual_xstream_pkgr_rs232rs485rfmodem_v5.x00.pdf (MaxStream X09-009PKC-R manual)
http://www.manuauto.com/decimal-to-hexadecimal-converter/ (Hex Converter)
© Copyright 2010, Manufacturers Automation Inc., www.manuauto.com
Manufacturers Automation Inc. 1600 King Street North P.O. Box 602 St. Jacobs, ON N0B 2NO 800-387-6268 Tel. 519-664-3300 Tel. 519-664-1600 Fax.
sales@manuauto.com