Automation and Device Networking – M.A.P.P.
Moxa NPort 5150 Bench Test
by Brent Raynor www.manuauto.com
RS-232 and RS-485 Port Test
Windows XP Setup
- Change the properties of the Local Area Connection.
- Go to Start,Settings, and then Network Connections.
- SelectLocal Area Connection andthenProperties.
- Scroll down the list and select Internet Protocol (TCP/IP).IfIP information is shownunderUse the following IP address, make sure to write it down before proceeding.
- Select Use the following IP address and enter an IP addressthat issimilar totheNPort 5110, except for the last two digits.
Hardware Setup
- Connectanethernet cross-over cable from the computer to the NPort 5150.
Moxa NPort Management Suite
-
The first step is to configure the ethernet side of theNPort 5110.
-
Open theNPort Management Suiteand select Configuration.


-
Select the NPort (MAC Adress) andconfigure the settings.
-
SelectNetworkand modify the IP Address, NetMask, and Gateway.

-
SelectSerial, then select Modify, double clicktheinformation line and select theSettings.

-
Set the baud rate to 9600, 8,N,1, No flow Control, enable FIFO. The Interface tab is eitherset toRS-232 or RS-485, 4 wire, depending on what signalis being tested.

- SelectOperation Mode, then select the Modify tab, double clicktheinformation line and selectView Settings tab. Set it for Real Com Mode.
- SelectOK and the settings will be updatedin the NPort 5110.


-
The next step is to configurethe com port.
-
SelectCOM Mappingand double clicktheinformation line to change the serial settings. If there is no information is shown, select Add Target.

-
Select the NPort required and click OK.


-
SelectBasicSettings and choose a com port.

-
SelectSerial Parametersand set for 9600,8,N,1, no flow control.Click OK.

-
SelectExit.

Reboot the computer at this point, before doing the loopback test.
HyperTerminal Loopback Test
TesttheRS-232communication port
- Jumperpins 2 to3on theMoxa NPort DE-311 DB9 com port.
- Pin 2 -> TXD Pin 3 -> RXD
- InWindows XP,go to start, programs,accessories,communications, and select HyperTerminal.
- Type aname for this project.
-
Select the com port that was assigned inRealCOM Installer.

-
Com port settings are 9600, 8, N, 1, None. Click OK.

-
Type a message and it willappearon theHyperTerminalscreen. ThisconfirmstheRS-232 communication portworks accordingly. Test this procedure by removing the jumper. As you type, the characters will notappear on theHyperTerminalscreen.
TesttheRS-422/485communication port
- Jumperpins 2 to3 and1 to 4 on theMoxa NPort DE-311 DB9 com port usingtwopaperclips.
- Pin 2 -> RXD+(B) Pin 3 -> TXD+(B)
- Pin 1 -> RXD-(A) Pin4 -> TXD-(A)
- Repeatthe HyperTerminal Loopback Test.
At Manufacturers Automation Inc., we are dedicated to customer service and want to make your experience with Moxaa pleasant one.
© Copyright 2010, Manufacturers Automation Inc., www.manuauto.com
Manufacturers Automation Inc. 1600 King Street North P.O. Box 602 St. Jacobs, ON N0B 2NO 800-387-6268 Tel. 519-664-3300 Tel. 519-664-1600 Fax.
StreetSmart 17X Ethernet Port Configuration
by Brent Raynor www.manuauto.com
How to configure the StreetSmart ethernet port
-
Connect an RS232 cable to COM O of the Adaptive StreetSmart controller board

-
Open the Diagnostic program in the AlphaNet software
-
Configure the Serial Settings, 9600, 8, N, 1 and select OK

-
Select Set Custom Commands

- Select Command 3
- Select Open Ini File

- Input the IP address and Subnet Mask
- Type under Command 3 in capital letters
- _01Z00_02EUi010.001.001.060_04
- Type under Command 4 in capital letters
- _01Z00_02EUs255.255.255.000_04
- Save and close
When entering the IP address or subnet mask make sure to enter three numbers before each dot. ie. 010.011.011.254

- Select Command 3 and the button will turn on.
- Click on Refresh and the IP address will update.
- Select Send (takes 30 seconds to update the EPROM)

- Confirm the IP address in StreetSmart display by typing _01Z00_02FUi_04
- Select Enter Your Own Command Text
- and after 30 seconds the changes will appear in the Results box

- Recycle power on the StreetSmart led display and the new IP address will appear on the diagnostic startup of the display.
At Manufacturers Automation Inc., we are dedicated to customer service and want to make your experience with Adaptive a pleasant one.