MOXA HDR-60-24 INTRODUCTION
The HDR-60-24 Power Supply Series has been specifically designed for industrial applications. The small form factor makes it ideal for installation in limited spaces, and the devices have been built to operate between -30 to 70°C. The devices have a plastic housing and support AC input ranges from 85 to 264 VAC and conform to the EN 61000-3-2 standard, which the European Union uses to regulate harmonic current. Furthermore, the devices are equipped with constant current mode for overload protection.
As an Authorized Distributor of MOXA, Manufacturers Automation Inc. (ManuAuto) offers a wide variety of Industrial Automation and Communication products across North America, including Canada (Ontario, Toronto) and the US. Buy the MOXA HDR-60-24 DIN-rail Power Supply online at a competitive price, with on-time delivery and fast shipping services. Our certified engineers are always available to support you.
MOXA HDR-60-24 CERTIFICATIONS

| Power Supply : Power Requirements | |
| Input | Voltage: 100 to 240 VAC (50 to 60 Hz), 120 to 370 VDC; Typical Current: 0.8 A @ 230 VAC, 1.2 A @ 115 VAC; Inrush Current (cold start): 60 A @ 230 VAC, 30 A @ 115 VAC |
| Operating Voltage | - |
| Output | Wattage: 60 W; Voltage: 24 VDC; Current Rating: 0 to 2.5 A |
| Over-voltage Protection | 30 to 36 V (Shut down operating voltage, repower on to recover) |
| Overload Protection | 105 to 160% (Constant current limiting, recovers automatically after fault condition is removed) |
| Reverse Polarity Protection | - |
| Power Supply : Physical Characteristics | |
| Dimensions | 52.5 x 90 x 54.5 mm (2.07 x 3.54 x 2.15 in) |
| Housing | Plastic |
| Weight | 230 g (0.5 lb) |
| Ambient Relative Humidity | 20 to 90% (non-condensing) |
| Operating Temperature | -30 to 70°C (-22 to 158°F), Max 45°C (113°F) |
| Storage Temperature | -40 to 85°C (-40 to 185°F) |
| Installation | DIN-rail mounting |
| Standards and Certifications | Safety: UL 508, EN 62368-1, UL 62368-1, IEC 62368-1; EMC: EN 55032/35, EN 61000-3-2 Class A, EN 61000-3-3, EN IEC 61204-3, EN IEC 61000-6-2; EMS: IEC 61000-4-2 ESD: Contact: 4 kV; Air: 8 kV, IEC 61000-4-3 RS: 80 MHz to 1 GHz: 10 V/m, IEC 61000-4-4 EFT: Power: 2 kV, IEC 61000-4-5 Surge: Power: 4 kV, IEC 61000-4-6 CS: 0.15 kHz to 80 MHz: 10 Vrms, IEC 61000-4-8 PFMF: 30 A/m, IEC 61000-4-11; MIL-HDBK-217F |
| MTBF | 927,560 hrs |
| Power Supply : Supported Series | |
| Supported Series | - |