PULS UC10.242 DC-UPS Control Unit
- Model: UC10.242
PULS UC10.242 FEATURES
- Built-in Capacitors as Energy Source (EDLC Electrochemical Double Layer Capacitors)
- Wide Temperature Range from -40°C to +60°C
- Typically >10 Years of Operational Lifetime Expectancy
- Regulated Output Voltage in Buffer Mode
- No Ventilated Cabinets Required (No Generation of Hydrogen as VRLA batteries do)
- Active Balancing for Longest Life and Buffer Times
- Short Charging Time, Unit is Rapidly Back in Ready Mode
- Output is Decoupled from the Input to Separate Load Circuits into Buffered and Non-buffered Sections
- Supports PC-Mode Function
PULS UC10.242 INTRODUCTION
The DIMENSION UC-Series are DC-UPSs utilizing
Electrochemical double-layer capacitors (EDLC),
commonly known as Ultracapacitors or Supercapacitors, installed inside the DC-UPS. They can bridge
power failures or voltage fluctuations and supply
voltage to the DC 24V bus for a certain period, which
allows for a safe shutdown of the system.
Expensive
downtimes, long restart cycles, and loss of data can be
avoided.
In times when the power supply provides sufficient
voltages, the DC-UPS stores energy in the capacitors. In
case of a mains voltage fault, this energy is released to
the DC bus in a regulated process.
The DC-UPSs are maintenance-free and have a similar
lifetime expectancy as power supplies. No regular
replacement of the capacitors is necessary, as is required
for battery-based DC-UPS systems. The wide
temperature range from -40°C to +60°C makes the unit
suitable for many applications.
The DC-UPSs come in two versions, which differ in the
size of the installed capacitors.
As an Authorized Distributor of PULS, Manufacturers Automation Inc. (ManuAuto) offers a wide variety of Industrial Automation and Communication products across North America, including Canada (Ontario, Toronto) and the US. Buy PULS UC10.242 DC-UPS Control Unit online at a competitive price, with on-time delivery and fast shipping services. Our certified engineers are always available to support you.
You can also find the UC10.241, UF20.481 models in the PULS DC-UPS and Buffer Modules With Capacitor Storage Series.
PULS UC10.242 CERTIFICATIONS

| PULS DC-UPS : Electrical Specifications | |
| Nominal Input Voltage | nom. 24 VDC |
| Input Voltage Ranges | DC: 22.5 to 30 VDC |
| Input Current | max. 17A |
| Output Voltage | nom. 24 VDC |
| Output Current | nom. 15A |
| Output Power | nom. 360W |
| Buffer Time | At 10A: 33s |
| Charging Time | 32 minutes |
| Power Losses | At 10A: 4.6W |
| Efficiency | typ. 97.8% |
| PULS DC-UPS : Protection Features | |
| Overvoltage Protection | Yes: typ. 32 VDC, max. 35 VDC |
| Reverse Polarity Protection | Yes: Max. –35 VDC |
| Short Circuit Protection | Yes |
| Over-Temperature Protection | Yes |
| Battery Discharge Protection | Yes |
| PULS DC-UPS : Battery | |
| Battery Voltage | - |
| Battery Voltage Range | - |
| Battery Charging Current | -- |
| Battery Discharging Current | - |
| Battery Charging Time | - |
| Allowed Battery Capacity | - |
| PULS DC-UPS : General | |
| MTBF | 850000 h |
| LED Indicators | 1 green LED |
| Relay Contacts | max. 60 VDC |
| Connection Method | Spring clamps |
| PULS DC-UPS : Physical Characteristics | |
| Operating Temperature | -40 to 60 °C |
| Storage Temperature | -40 to 70°C |
| Relative Humidity Range | 5 to 95% r.H |
| Altitude Range | 0 to 6000m |
| Dimensions | 198 mm x 124 mm x 117 mm |
| Weight | 1720 g |
| Mounting Type | DIN rail |
| Housing | - |
| Standards and Certifications | EAC, KC, WEEE, REACH, EU, VDMA 24364, ISA-71.04 G3, IEC 60068-2-60, Marine (ABS), Marine (DNV), Class I Div. 2, Class I Div 2, IECEx, ATEX, UL 60950-1, IEC 60950-1, UL 508, IEC 60068-2-6, IEC 60068-2-27 |